پمپ آتش نشانی برند EBITT مدل AUED MGHE
(EBITT Brand AUED MGHE)
Construction EBITT AUED MGHE
EN12845 Fire pump stations constructed for feeding water to automatic fire fighting systems and units with hydrants and sprinklers.
Units are composed of 1 or 2 main pumps and one jockey pump set with which the system pressure level can be maintained without having to start the main pump(s).
Operation
The pumps start operating after a fall in the pressure level in the fire extinguishing system.
The first pump to be triggered is the jockey pump in the station.
If this pump cannot restore the pressure level, then the main pumps starts.
When there is more than one main pump, the pumps start in cascade sequence with the starting pressure switches set at different pressure levels.
The pressure switches of the main pumps are used for automatic starting as the pumps must be stopped manually as per EN12845 standards.
The test loop or recirculation diaphragm allows for operation of the main pumps also when the delivery port is closed (with no consumption of water in the system), avoiding overheating of the
water inside the pump body.
Weekly test system is included in fire pump stations.
The membrane type of expansion tank with the capacity of 24 liters-16 bar execution is being mounted in fire pump set for absorbtion of water hammer.
Pumps
Ebitt EL series of main pumps are being used. Horizontal, end-suction, single staged centrifugal pumps are being used in fire pump station.
Standard delivery is cast iron execution with mechanical sealing.
Optionally bronze fitted execution or soft gland packing sealings are being used.
Couplings of main pumps are;
- Elastic couplings for electric driven sets (optionally spacer type couplings)
- Universal joints-cardan shafts for diesel driven sets.
Jockey Pumps are;
MV series: Vertical, multi-staged, stainless steel constructed off-line centrifugal pumps.
XVM series: Vertical, multi-staged, stainless steel constructed inline centrifugal pumps.
All pumps are mechanical sealed.
The maximum pressure developed by the jockey pump is always greater than the pressure of the main pumps.
Electric Motors:
- ۲-pole induction type, 50 Hz, n=2900 rpm, IEC standardized, TEFC Type
- Three-phase 230/400V +/-10% up to 3 kW, 400/690V +/-10% 4kW and higher
- Insulation Class F
- Protection Class IP55
- Construction in accordance with IEC 60034
- Other voltage and frequency ratings and ambient temperatures available on request.
Diesel Engines:
Diesel engines are direct-injection types fitted with electric control box, fuel tank, 2 re-chargeable batteries, exhaust silencer and internal cooling system loop complete with wiring harness and cabling.
Emission data, noise levels are complying to EN12845 standards, the sets are certified according to EN standards.
Hydraulic Components
- All pumps in fire pump stations are being delivered on a common base plate with suction and discharge manifolds.The suction manifold is never supplied as such execution is forbidden by the standard.
- Each main pump has its own eccentric reducer + butterfly valve with gear box + check valve at discharge side. Diesel driven main pump has additionally rubber expansion joint.
- Outlet manometer is fitted on discharge manifold.
- There are 2 Pressures switches (2 for each pump) in the unit.
- Manual test circuit with pressure switches, pressure gauge, non-return valve and ball valve and 24 liters expansion tank complete with pressure relief valve.
- Jockey pump is fitted with inlet/outlet valves and check valve
- All the pumps and control panel for each pump in the unit are fitted on the common base plate with internal cabling and jockey pump control panel has dry running protection float switch.
Electric Boxes
Electric Fire Pump Controller as per EN12845 This equipment enables automatic or manual management of an electric Start-delta starting pump according to the standards UNI EN12845:2009.
They are assembled in painted sheet metal housing with IP55 protection class and made in accordance with the CEI standards in force.
- Electric Star-Delta starting pump electromechanical panel.
- Mains input 3~50/60 Hz 400V+/-10%
- ۴۰۰V/24V transformer for auxiliary circuits
- Very low voltage input for control via 2 caller/running pressure switches (NO contact with pressure system and electric pump stationary: on closure of the contact the pump starts up)
- Very low voltage input for signal from electric pump pressure switch in pressure/running (NO contact with pressure system and electric pump stationary)
- AUTOMATIC-0-MANUAL (EMERGENCY) key operated selector switch (key removable in AUT position): in AUTOMATIC position electric pump startup via signals from caller pressure switches; in MANUAL(EMERGENCY) position electric pump start-up manual by means of START/STOP buttons; in “۰” position, pump start-up disabled.
- Selector P1 DISABLED-“۰”-P2 DISABLED : In position P1 DISABLED the caller pressure switch P1 DISABLED; in position 0 no caller pressure switch is disabled; in position P2 DISABLED caller pressure switch P2 is disabled
- Electronic control unit for electric pump management
- Pump START/STOP buttons for manual test
- Control unit indicator light test button
- Buttons to display electrical parameters
- Voltmeter, ammeter digital three-phase watt meter
- Green pump ON indicator (from pump running pressure switch signal)
- Power ON green indicator light
- Red indicator light for pump start request from caller pressure switch
- Yellow indicator light for pump start request from priming tank float
- Yellow indicator light for pump start-up failure
- Yellow indicator light for automatic start-up disabled
- Green indicator light for weekly test in progress
- Operating system according to UNI10779 with settable timed delay of pump shutdown
- Pump running detection (from pump running pressure switch) with settable delay
- Electric pump control contactors sized to AC3
- Timed, settable Star-Delta contactor switching
- Auxiliary protection fuses
- Motor overload cutout high capacity fuses
- General disconnect switch with door lock
- Alarm output with changeover contact (max 5A 250V AC1) for signal “ELECTRIC POWER AVAILABLE”
- Alarm output with changeover contact (max 5A 250V AC1) for signal “PUMP RUNNING”
- Alarm output with changeover contact (max 5A 250V AC1) for signal “START-UP REQUEST”
- Alarm output with changeover contact (max 5A 250V AC1) for signal “START-UP FAILURE”
- Alarm output with changeover contact (max 5A 250V AC1) for signal “PRESSURE SWITCH DISABLED”
- Metal casing
- Tear-proof cable clamp output
- IP55 Protection rating
- Ambient temperature: -5/+40°C
- Relative humidity 50% at 40°C (condensate free)
Diesel Driven Pump Controller
- Electromechanical control panel for diesel pump
- Input voltage 1~50/60 Hz 230V -/+ 10%
- Input from 2 pieces external lead batteries for control of the starting motor and supply of auxiliary circuits
- Very low voltage input for control from 2 pieces call/start pressure switches in series (NC contact with system in pressure and diesel pump stopped)
- Very low voltage input for control of the diesel pump from float switch in priming tank (NO contact with tank full of water)
- Very low voltage input for signaling of electric pump in pressure/on from pressure switch (NO contact with diesel pump control)
- Selector with key AUT-MAN in automatic position starting of the diesel pump by electronic unit in MANUAL position starting of the diesel pump by start push button of the electronic unit
- Pushbuttons for manual start of the diesel pump
- Pushbutton for restoring from anomalies
- Pushbutton for testing the manual shut off of the diesel pump
- Pushbutton for test of the electronic unit’s lights
- Pushbutton for scrolling the functions of the unit
- Pushbuttons for Manual Emergency protected by “Safe crash”
- LCD Display for the visualization of 2 pieces batteries’ voltmeters, 2 pieces batteries’ ammeters, round meters, total run meter, partial run meter, indicator of fuel level, water thermometer, oil thermometer, oil manometer, batteries starting counter, history of the events
- Signaling lights
- Operation mode according to UNI10779 with timer for delay of stop of the pump adjustable from 1’ to 30’
- Visualization of the display settable in 5 languages: Italian, English, Spanish, German, French
- Functions of delay and specific alarms settable from electronic unit
- ۲ pieces battery charges 12Vdc 3A (24Vdc 3A for 24V
- Auxiliary protection fuses
- Main switch with interlocking door
- Alarm output with exchangeable contact (max 5A 250V AC1) for signaling of “AUTOMATIC OPERATION EXCLUDED”
- Alarm output with exchangeable contact (max 5A 250V AC1) for signaling of “CONTROL PANEL BREAKDOWN”
- Alarm output with exchangeable contact (max 5A 250V AC1) for signaling of “DIESEL PUMP OPERATING”
- Alarm output with exchangeable contact (max 5A 250V AC1) for signaling of “START FAILED”
- Steel enclosure
- Output with cable holder
- Protection IP55
- Ambient temperature: -5°C/+40°C
- Relative humidity 50% at 40°C (not condensed)
Jockey Pump Controller (DJ)
DJ is designed for controlling 1 jockey pump used.
This cabinet contains the electronic control card with microprocessor, for managing pump operation.
The microprocessor carries out continuous secure checks during all the various work phases of the pump and incorporates all necessary functions, thus reducing electrical and electronic components inside.
The pump starts automatically when reaches at upper pressure set value and stops also when there is no water in the suction.
Technical Features EBITT AUED MGHE
- Electronic control panel
- Power supply 3~50/60 Hz 400V -/+ 10%
- Control input from NO contact (float/pressure switch)
- Input for motor winding thermal protection
- Sensors suitable for use with not flammable conductive fluids (not included)
- Incorporated sensor sensitivity adjustment
- Push buttons for operating motor in “Automatic-Off-Manual” modes
- “Mains power on” LED
- “Alarm” LED for min/max water level
- “Motor on” LED
- “Motor protection enabled” LED
- “Automatic” LED (this is on the automatic push-button)
- Restore protection button
- Adjustable motor protection (Motor Current Trimmer: 2<> 22A or 20<> 44A)
- Protection activation time 5”
- Incorporated dip-switch for overriding the “Motor cut-out”(dip-switch 4)
- Internal “Sensors alarm” cut off switch (jumper ESC. TIM. TA)
- Motor protection fuses
- Auxiliary protection fuse
- Alarm output with switching NO-C-NC contacts, capacity 16A 250V (resistive load)
- Single-phase version adapted for the insertion of a capacitor (not included)
- Main circuit-breaker with door luck
- Output with cable clamps
- ABS box
- Protection IP55
- Ambient temperature: -5/+40°C
- Relative humidity 50% at 40°C (condensate free)