توضیحات
پمپ آتش نشانی برند EBITT مدل FIREPAK-E21 & FIREPAK-ED21
(EBITT Brand Fire pumps set model FIREPAK-E21 & FIREPAK-ED21)
Description EBITT FIREPAK-E21 & FIREPAK-ED21
Designation of Fire Pumps Set
FIREPAK – E 2 1 – 120 / 80 – WTM 80-250 / 55 + DJ MV
FIREPAK: Package Type Fire Pumps Set
E: All pumps in the set electric driven
۲: No. main pumps
۱: no. jockey pump
۱۲۰: Rated Flow per main pump (m3/h)
۸۰: Rated Pressure (Hm)
WTM 80-250/55: 1 main + 1 stand by pump
DJ MV: Jockey Pump Set
FIREPAK – ED 2 1 – 120 / 80 – WTM 80-250 / 55 + EKM 4102 + DJ MV
FIREPAK: Package Type Fire Pumps Set
ED: 1 electric main + 1 diesel driven stand by pump
۲: No. main pumps
۱: no. jockey pump
۱۲۰: Rated Flow per main pump (m3/h)
۸۰: Rated Pressure (Hm)
WTM 80-250/55: Electric driven main pump
EKM 4102: Diesel Driven Main Pump
DJ MV: Jockey Pump Set
Construction
Fire pumps set constructed for feeding water to automatic fire fighting systems and units with hydrants and sprinklers.
Units are composed of 2 main pumps and one jockey pump set with which the system pressure level can be maintained without having to start the main pumps.
The main pumps are always one active + 100% one stand by, and stand by main pump can be either electric driven or diesel driven.
Operation
The pumps start operating after a fall in the pressure level in the fire extinguishing system.
The first pump to be triggered is the jockey pump in the set.
If this pump cannot restore the pressure level, then one of main pumps starts.
Since there is more than one main pump, the pumps start in cascade sequence with the starting pressure switches set at different pressure levels.
The pressure switches of the main pumps are used for automatic starting and adjustable time automatic stopping.
Weekly test system is included in the sets which are above 7,5 kW main pumps’ power.
The membrane type of expansion tank with the capacity of 24 liters-16 bar execution is being mounted in fire pumps set for the absorbtion of water hammer.
Pumps
Main pumps are:
NMD Series: Horizontal, Monoblock, end-suction, bronze fitted centrifugal pumps
WTM Series: Horizontal, close-coupled, end-suction, centrifugal pumps For NMS and WTM pumps; our standard delivery is cast iron execution.
Bronze fitted executions are optional.
Jockey Pump is:
TP Series: Horizontal, monoblock, peripheral constructed centrifugal pumps
MV series: Vertical, multi-staged, stainless steel constructed off-line centrifugal pumps.
All pumps are mechanical sealed.
The maximum pressure developed by the jockey pump is always greater than the pressure of the main pumps.
Electric Motors:
- ۲-pole induction type, 50 Hz, n=2900 rpm, IEC standardized, TEFC Type
- Three-phase 230/400V +/-10% up to 3 kW, 400/690V +/-10% 4kW and higher
- Insulation Class F
- Protection Class IP55
- Construction in accordance with IEC 60034
- Other voltage and frequency ratings and ambient temperatures available on request.
Diesel Engines:
Diesel engines are equipped with NMD, NMS and WTM series of our pumps.
They are direct-injection types fitted with electric control box, fuel tank, starter battery and exhaust silencer.
The cooling of engine can be by air, or water cooled by internal cooling system loop.
Hydraulic Components
- All pumps in fire system are being delivered on a common base plate with suction and discharge manifolds as a package type, ready for use.
- The controllers of pumps are also being mounted ın this common base plate complete with internal cabling between controllers and motors/ engines.
- Each main pump in the system has its own eccentric reducer + butterfly valve at suction side and concentric reducer + butterfly valve + check valve at discharge side.
- Manometer is fitted on discharge manifold.
- Pressures switch one for each pump in the set, and expansion tank is being mounted on discharge manifold.
- Jockey pump is fitted with inlet/outlet valves and check valve and dry running protection float switch equipped in its controller on the common base plate of fire pumps set.
Electric Boxes
Firepak -E21 Fire Pumps Set Electric Controller features are as follows;
This equipment enables automatic or manual management of an electric Start-delta starting pump according.
They are assembled in painted sheet metal housing with IP55 protection class and made in accordance with the CEI standards in force.
- Electric Star-Delta starting pump electromechanical panel.
- Mains input 3~50/60 Hz 400V+/-10%
- ۴۰۰V/24V transformer for auxiliary circuits
- Very low voltage input for control via 1 caller/running pressure switches (NO contact with pressure system and electric pump stationary: on closure of the contact the pump starts up)
- Very low voltage input MIN LEVEL FLOAT SWITCH
- AUTOMATIC-0-MANUAL (EMERGENCY) selector: in AUTOMATIC position electric pump start-up via signals from caller pressure switch; in MANUAL(EMERGENCY) position electric pump start-up manual by means of START/STOP buttons; in “۰” position, pump start-up disabled.
- Pump MANUAL START selector for manual test
- Voltmeter and ammeter
- Green light for motor on
- Red light for THERMAL PROTECTION
- Blue light for POWER SUPPLY
- Settable timed delay of pump shutdown
- Electric pump control contactors sized to AC3
- Timed, settable Star-Delta contactor switching
- Timer for weekly test (optional)
- Motor protection fuses
- Current transformer for 1 phase
- Auxiliary protection fuses
- General disconnect switch with door lock
- Alarm output with contact for signal “MOTOR ON”(C-NC-NO)
- Alarm output with contact for signal “THERMAL PROTECTION” (C-NC-NO)
- For jockey pump** (**:go to last Line)
- Metal casing
- Output with cable holder
- IP55 Protection rating
- Ambient temperature: -5/+40°C
- Relative humidity 50% at 40°C (condensate free) Diesel Engine Pump Controller-Firepak ED21
- Electromechanical control panel for diesel pump
- Input voltage 1~50/60 Hz 230V 8A max
- Input from 1 piece external lead batteries for control of the starting motor and supply of auxiliary circuits
- Very low voltage input for control from 1 pieces call/start pressure switches in series
- Electronic unit for diesel pump control
- Selector with push button AUT-MAN, in automatic position starting of the diesel pump by electronic unit in MANUAL position starting of the diesel pump by start push button of the electronic unit
- Pushbuttons for manual start of the diesel pump
- Pushbutton for manual shut off of the diesel pump
- Pushbutton for scrolling the functions of the unit
- With the running engine, the engine instruments are in the event of a fault instead of the measurement, the display shows the message of the occurred fault.
– Battery voltmeter
– Totalhour meter
– Partial hourmeter
– Starting counter
– Starting failures counter
– Fuel level indicator
– Tachometer - Simultaneous reading of the instruments with the running engine, fuel level indicator, tachometer, hour-meter
- Automatic faults surveillance with messages on the display
- Texts in 6 languages: Italian, English, French, German, Spanish and Portuguese
- Glow plugs preheating management or engine heating cooling
- Preventive maintenance warning
- Programmable weekly selftest
- Available fully programmable input for anomaly or water pump protection (Protection device used in irrigation systems)
- CAN Bus SAE J1939
- Possibility of starting the engine when the charge of the battery is low
- Anomaly historical record (including data from the last 100 occurred anomalies)
- Signaling lights
- With timer for delay of stop of the pump adjustable
- Auxiliary protection fuses
- Main switch with interlocking door
- General alarm output contact
- Box in ABS or metallic box
- Output with cable holder
- Protection IP54
- Ambient temperature: -5°C/+40°C
- Relative humidity 50% at 40°C (not conden
**:
- – Control input from NO contact (pressure switch)
- Alarm control input from NO contact (float/pressure switch)
- Input for motor winding thermal protection
- Push buttons for operating motor in “Automatic-Off-Manual” modes
- “Mains power on” LED
- “Alarm” LED for min/max water level
- “Motor on” LED
- “Motor protection enabled” LED
- “Automatic” LED (this is on the AUTOMATIC push-button)
- Restore protection button
- Adjustable motor protection (motor current trimmer: 2 <> 22A or 20 <>44A)
- Protection activation time: 5”
- Alarm output with switching NO-C-NC contacts, capacity 16A 250V (resi stive load)
- Single phase version adapted for the insertion of a capacitor (not included)